Managing a building with a heating, ventilation and air conditioning system that is obsolete and inefficient, the board of Eaglestone Lodge is facing making improvements expected to cost $300,000.
Lodge
EAGLESTONE LODGE PERSONAL CARE HOME

聽 聽 聽 聽 聽 聽 Managing a building with a heating, ventilation and air conditioning system that is obsolete and inefficient, the board of Eaglestone Lodge is facing making improvements expected to cost $300,000.

聽聽聽聽聽聽聽聽聽聽聽 鈥淲e鈥檙e probably looking at a several-years plan with long-term funding,鈥 Dave Clark, who has been a board member since last April, said last week after releasing a system audit report submitted by Kontzamanis Graumann Smith MacMillan Inc. (KGS Consulting) of Regina.

聽聽聽聽聽聽聽聽聽聽聽 Eaglestone Lodge Personal Care Home, which opened in 1958, is a long-term care facility in Kamsack for adults who require care due to infirmity from age, chronic illness and/or disability. As of last week, the lodge had 48 full care and independent living residents with two independent living vacancies.

The Lodge is a registered charitable non-profit organization, which does not receive funding for operations or maintenance from SaskHealth, Clark said. 鈥淚t seems a lot of people don't realize this.鈥

聽聽聽聽聽聽聽聽聽聽聽 Although the board has not yet prioritized the recommendations, Clark said he expects that the room ventilation will probably be among the first aspects of the system to be improved.

聽聽聽聽聽聽聽聽聽聽聽 The HVAC (heating, ventilation, air conditioning) report submitted by KGS Consulting said that the Lodge鈥檚 鈥渆xisting boilers are past their life span and not operating as efficiently as they could be. The boiler/HVAC control system is inadequate and does not provide efficient temperature control of the occupied space.

聽聽聽聽聽聽聽聽聽聽聽 鈥淭he existing exhaust fans are past their life span and not operating as efficiently as they could be,鈥 it said. 鈥淭he fan controls are inadequate for energy/heat conservation with excessive amounts of heated air being exhausted to the outdoors.

聽聽聽聽聽聽聽聽聽聽聽 鈥淭he existing hydronic heating loop has inadequate zoning and controls to maintain proper occupied space temperature based on user requirements,鈥 it said. 鈥淧iping and radiators are aging and should be considered for replacement in the near future.

聽聽聽聽聽聽聽聽聽聽聽 鈥淭here is no direct supply air flow to individual rooms. Air is transferred from the main hallways into the rooms through under cuts on the doorways. This is not good practice.

聽聽聽聽聽聽聽聽聽聽聽 鈥淒uctwork is in very poor condition with joints not being sealed, insulation compromised and duct supports failing in various locations.

聽聽聽聽聽聽聽聽聽聽聽 鈥淔resh intake air ducting proximity to the ground and the height at which they were installed allows them to be readily covered with snow in wintertime and in summer when the rain saturates the soil, off gases from the saturated soil is a strong pungent smell and evident inside the mechanical room. This also provides poor air quality being supplied throughout the occupied spaces.鈥

聽聽聽聽聽聽聽聽聽聽聽 In order to improve the situation, KGS Consulting recommends the replacement of the existing boiler systems within the mechanical room. Payback from the replacement was estimated at 4.5 years.

聽聽聽聽聽聽聽聽聽聽聽 聽It recommends the replacement of the existing roof exhaust fan system to a zoned exhaust fan system, utilizing occupancy sensors within the washrooms for both lighting control and fan control, it said. 鈥淭his would remove the 24-hours-a-day, seven-days-a-week operation resulting in needless energy consumption and retention of a fair majority of lost building heat through the current exhaust system.鈥

聽聽聽聽聽聽聽聽聽聽聽 The replacement of all existing ductwork and duct insulation due to its poor condition was recommended. 鈥淎ll ducting supports should be replaced as well.鈥

聽聽聽聽聽聽聽聽聽聽聽 The current hydronic heating loop throughout the building should be upgraded to re-zone rooms and areas based on occupancy, using individual thermostats, zoning valves, modification to piping within crawlspace with a dedicated re-circulation pumping system and piping to improve efficiencies within the heating system, it said. 鈥淚nsulated piping, zone return valves and thermostats for the zones with individual comfort and allowance for premium room control that communicate back with a centralized controller would be extremely beneficial.鈥

聽聽聽聽聽聽聽聽聽聽聽 Additional ventilation is needed for all rooms/suites and areas identified as required by guidelines for correct air exchanges and improved air quality for the entire facility, it said.

A complete thermal scan of the entire facility to recognize heat losses through building envelope should be considered and that would assist in energy conservation applications for the facility, it said. At present the windows and doors throughout have been identified as major heat source losses and should be upgraded to a better efficiency rating to provide for an increased saving on operations budgets.

鈥淭here would be a requirement to upgrade the current electrical system throughout the building to meet or exceed code requirements for long-term care facilities,鈥 it said. 鈥淯pgrading lighting throughout to an automated system and incorporating energy efficient fixtures and controls would provide cost savings. This would require an electrical engineer to conduct a more thorough evaluation of the existing system.鈥

Clark, who received the report in mid-December, said that the board has yet to act on its recommendations but was eager to inform the community鈥檚 residents what it is facing with regards to the lodge鈥檚 heating, ventilation and air conditioning requirements.聽